Airborne Molecular Contamination (AMC)/Gas Phase filtration (GPF)
Increasingly in controlled environments the presence of molecular levels of
contamination in the air is damaging to the process being performed. The requirements
in high end semiconductor processes are currently being joined by Hard Disc
manufacturing and Life Sciences/Pharmaceutical. In some cases the customers need is
so critical that the entire facility is filtered for AMCs but due to the very high cost of
this approach it is more common that only the most critical process steps are filtered for
AMCs, and this approach involves specialty Fan Filters. Typically 3 steps are involved
in the successful implementation of an Airborne Molecular Contamination (AMC) removal program.
- Determine the AMC specie(s) that are causing your process the problems you are
observing. TES can assist you in sourcing qualified labs to do this work. Geography
would play a roll in our referral process to a qualified lab, but typically we would
recommend Balasz Labs in Fremont, Ca.
- After the species and concentration levels are known then we can involve one of
several high end strategic partners we work with to define and specify the actual
AMC product, taking into account your desire for removal efficiency, expected life,
and price point. At the end of this step we will have a product specified that will
remove a guaranteed amount of the species for a guaranteed amount of time. PHD
scientists provide all the data and the main deliverable is a chart of expected filter
life, and efficiency during that lifetime
- Design and deliver a custom FFU product that will deliver AMC and particulate air into the
clean space.
Why can’t I just use the FFUs I have at my facility with the AMC filters?
- Several factors make it unlikely that any standard FFU will work when adding
AMC filtration The fan in the FFU is sized only for the resistance of the HEPA filter/
30% pleated prefilter combination and the addition of a very restrictive filter such as a
high end AMC filter would cause the unit to flow at only a small fraction of it’s normal
flow
- The AMC filters work based on residence time of the air with the AMC media and
since common “construction style” FFUs, like the Envirco MAC-10, have a single
fan inlet the flow through an AMC filter would be to high to allow them to work at
the high efficiencies they are designed to work at.
TES/Airflotek has a wealth of experience in applying AMC filters to custom applications,
and there are a number of hurdles to clear that a less experienced FFU provider will not
likely to be familiar with. Subjects like designing filter inlet uniformity so the AMC
filters will realize their potential for removal efficiency and life are key to a successful
AMC filter application. We maintain strategic partnerships with all the major suppliers of
AMC filters who’s products include:
- Camfil’s Gigapleat
- Donaldson’s Broad Spectrum Max and Chemcore
- Entegris’s Vaporsorb
- Purafil’s GridBlok
- American Air Filter’s SAAF media
Depending on your need to remove AMC from key process steps, we can recommend
and provide effective AMC removal with your FFU.
Or, conversely, if you have defined an AMC problem we can design a solution, complete
with the AMC filter that will guarantee the result you need..